Reactor shutdown
A reactor is considered to be shut down when it is subcritical and sufficient shutdown reactivity exists so there is no immediate probability of regaining criticality. Shutdown is normally accomplished by insertion of some (or all) of the control rods, or by introduction of soluble neutron poison into the reactor coolant.
The rate at which the reactor fission rate decays immediately following shutdown is similar for all reactors provided a large amount of negative reactivity is inserted. After a large negative reactivity addition the neutron level undergoes a rapid decrease of about two decades (prompt drop) until it is at the level of production of delayed neutrons. Then the neutron level slowly drops off as the delayed neutron precursors decay, and in a short while only the longest-lived precursor remains in any significant amount. This precursor determines the final rate of decrease in reactor power until the neutron flux reaches the steady state level corresponding to the subcritical multiplication of the neutron source.
The half-life of the longest lived delayed neutron precursor results in a reactor period of around -80 seconds or a startup rate of -1/3 DPM for most reactors after a reactor shutdown. One noticeable exception to this is a heavy water reactor. In a heavy water reactor, the photoneutron source is extremely large after shutdown due to the amount of deuterium in the moderator and the large number of high energy gammas from short-lived fission product decay.
The photo-neutron source is large enough to have a significant impact on neutron population immediately after shutdown. The photo-neutron source has the result of flux levels decreasing more slowly so that a heavy water reactor will have a significantly larger negative reactor period after a shutdown.
Throughout the process of reactor shutdown the nuclear instrumentation is closely monitored to observe that reactor neutron population is decreasing as expected, and that the instrumentation is functioning properly to provide continuous indication of neutron population. Instrumentation is observed for proper overlap between ranges, comparable indication between multiple instrument channels, and proper decay rate of neutron population.
A distinction should be made between indicated reactor power level after shutdown and the actual thermal power level. The indicated reactor power level is the power produced directly from fission in the reactor core, but the actual thermal power drops more slowly due to decay heat production as previously discussed. Decay heat, although approximately 5 to 6% of the steady state reactor power prior to shutdown, diminishes to less than 1% of the pre-shutdown power level after about one hour.
After a reactor is shutdown, provisions are provided for the removal of decay heat. If the reactor is to be shut down for only a short time, operating temperature is normally maintained. If the shutdown period will be lengthy or involves functions requiring cooldown of the reactor, the reactor temperature can be lowered by a number of methods. The methods for actually conducting cooldown of the reactor vary depending on plant design, but in all cases limitations are imposed on the maximum rate at which the reactor systems may be cooled. These limits are provided to reduce the stress applied to system materials, thereby reducing the possibility of stress induced failure.
Although a reactor is shut down, it must be continuously monitored to ensure the safety of the reactor. Automatic monitoring systems are employed to continuously collect and assess the data provided by remote sensors. It is ultimately the operator who must ensure the safety of the reactor.
|
|